The primary output of a Reservoir is its Value. The Display Units determine the dimensions of this output. The primary output of a Reservoir is always a value (it cannot be a condition), but can be specified as a scalar, a vector or a matrix. You can specify the order by pressing the Type… button. By default, the primary output of a new Reservoir element is a scalar, dimensionless value.
Note: GoldSim encourages (but does not require) you to specify Display Units for a Reservoir whose dimensions are consistent with materials. In particular, it expects the units to have dimensions of mass, volume, energy, amount, currency, or to be dimensionless. When you first specify your Display Units, GoldSim will warn you if your units do not have one of these dimensions. GoldSim will not, however, prevent you from using other units.
The Initial Value input to the Reservoir must have the same attributes (order and dimensions) as the primary output.
Note: The Initial Value must be a number or a link from a static variable (e.g., a constant Data element or a Stochastic).
There are two Rate of Change inputs: one representing Additions and one representing Withdrawal Requests. These inputs must have the same order (i.e., scalar, vector, matrix) as defined for the element. Moreover, the dimensions must represent a rate of change of the primary output (e.g., if the primary output has units of mass, the Rate of Change inputs must have units of mass per time).
The Rate of Change inputs must be entered as non-negative values. Negative values for these inputs during a simulation will result in a fatal error.
Note: The specified Rate of Change inputs represent constant rates over the next timestep. Hence, if an Rate of Change was defined as “if(time > 10 day, 2 m3/day, 1 m3/day)”, and you were using a 1 day timestep, the rate would not actually change to 2 m3/day until time = 11 days. That is, since at time = 10 days, the if statement indicates that the rate is equal to 1 m3/day, GoldSim would assume that the rate was equal to 1 m3/day between 10 days and 11 days. If you wanted the rate to change at 10 days, you would write the if statement as “if(time >= 10 day, 2 m3/day, 1 m3/day)”.
Note: If the output of a Reservoir is specified as being an array (a vector or a matrix), the Initial Value and Rate of Change inputs must, by definition, themselves be arrays. Since you often may wish to enter a zero array (a vector or matrix of zeros) for one or more of these inputs, GoldSim allows you to leave any of these input fields blank, in which case it interprets the field as a zero array.
Learn more about: